1Name of Regulation
This Regulation is the Gas Supply (Safety and Network Management) Regulation 2022.
This Regulation is the Gas Supply (Safety and Network Management) Regulation 2022.
This Regulation commences on 1 September 2022.
Note—
This Regulation replaces the Gas Supply (Safety and Network Management) Regulation 2013, which is repealed on 1 September 2022 by the Subordinate Legislation Act 1989, section 10(2).
The Dictionary in Schedule 2 defines words used in this Regulation.
Note—
The Act and the Interpretation Act 1987 contain definitions and other provisions that affect the interpretation and application of this Regulation.
For the Act, Dictionary, definition of basic metering equipment, the following equipment is prescribed—
valves to isolate gas supply,
pipe work, including a combination of pipes, flanges, tees, elbows and other pipe-connecting equipment designed to convey gas,
fittings, smaller instruments used in connection with fittings, pressure sensing tubing and tube fittings, instrument valves and associated equipment,
filters designed to trap and remove foreign matter from gas streams,
pressure regulators designed to reduce and control pressure,
over-pressure protection devices designed to protect downstream equipment from exposure to excessive pressure if upstream equipment fails,
non-return valves designed to ensure gas flow travels in only one direction and to prevent reverse flow,
mechanical indexes designed to indicate consumption of raw metered gas,
meter bars and other equipment designed to support a gas meter, and associated equipment that forms part of the meter installation,
electrical connections and wiring designed to convey electrical signals for gas meters, flow correction devices, alarms and metering communications equipment,
flow correction devices or software designed to enable raw metering data to be—
adjusted for the effects of temperature, pressure or gas quality, and
referenced to standard temperature and pressure conditions,
temperature and pressure correction devices designed to enable raw metering data to be adjusted for the effects of temperature and pressure,
devices and equipment designed to analyse and calculate the heating value of a gas stream.
Example—
Chromatography equipment and calorimeters.
For the Act, Dictionary, definition of gas, paragraph (c), each of the following is declared to be a gas—
hydrogen gas that is not mixed with another gas,
a mixture of hydrogen gas and either natural gas or liquefied petroleum gas.
For the Act, Dictionary, definition of natural gas, a substance that satisfies the following is prescribed—
the substance is in a gaseous state at standard temperature and pressure,
the substance consists of hydrocarbons, or a mixture of hydrocarbons and non-hydrocarbons, the principal constituent of which is methane,
the substance has been processed or otherwise dealt with to make it suitable for consumption.
A network operator must develop, maintain and operate a safe gas network.
Maximum penalty—
for a corporation—10,000 penalty units, or
for an individual—5,000 penalty units.
A network operator must, when designing, constructing, operating or extending a gas network or part of a gas network, take into account all relevant standards.
Maximum penalty—
for a corporation—10,000 penalty units, or
for an individual—5,000 penalty units.
In this section—
relevant standards means the codes, Australian Standards, guidelines or other requirements specified in a written notice by the Secretary to the network operator.
A network operator must, within 7 days after the date of the grant of an authorisation or licence to operate a gas network, nominate a contact person (the person-in-charge) for the gas network by written notice to the Secretary.
Maximum penalty—
for a corporation—250 penalty units, or
for an individual—100 penalty units.
The person-in-charge must be competent and specifically authorised by the network operator to communicate with the Secretary about, and make decisions about, the maintenance, repair and operation of the network operator’s gas networks.
Within 7 days after a person ceases to be a person-in-charge, the network operator must nominate another person to be the person-in-charge by written notice to the Secretary.
Maximum penalty—
for a corporation—250 penalty units, or
for an individual—100 penalty units.
A written notice required by this section must include the full name and contact details of the person-in-charge, including a telephone number on which the person-in-charge may be contacted outside ordinary working hours.
A person who was a network operator immediately before the commencement of this Regulation must nominate, by written notice to the Secretary, a person-in-charge for the network operator’s gas network within 30 days of the commencement of this Regulation.
Maximum penalty (subsection (5))—
for a corporation—250 penalty units, or
for an individual—100 penalty units.
A network operator must do the following—
provide the public with an emergency telephone number, available every day for 24 hours a day, for reporting an escape of gas from—
the network operator’s gas network, or
gas pipe work within premises directly connected to the gas network,
provide the public with a way of reporting an escape of gas in person, during normal business hours, at the network operator’s business premises,
provide an effective system for receiving and dealing with reports, including ensuring every report is promptly acted on,
ensure, as far as possible, everything is done that needs to be done to stop the escape of, and to disperse, gas that—
is at risk of igniting or exploding, or
risks suffocating or otherwise harming a person,
ensure the ways in which the network operator can be contacted for the purpose of reporting an escape of gas are adequately publicised,
make available, on request, the details of the network operator’s emergency services, including a statement to the effect that the operator will make safe an escape of gas from—
its gas network, and
the part of a consumer service directly connected to its gas network, up to and including the gas meter outlet.
Maximum penalty—
for a corporation—10,000 penalty units, or
for an individual—5,000 penalty units.
This section applies to—
work involving the installation or replacement of a gas meter or another part of the basic metering equipment, and
the installation, alteration, extension or repair of, or other work on, a consumer service.
A person must not carry out work to which this section applies other than in accordance with the requirements of the network operator rules for the gas network to which the work relates.
Maximum penalty—
for a corporation—2,000 penalty units, or
for an individual—100 penalty units.
A person who carries out work to which this section applies that is not done on behalf of the network operator for the gas network to which the work relates—
must—
be the holder of a licence under the Home Building Act 1989 authorising its holder to contract to do the work, or
be carrying out the work on behalf of an individual, partnership or corporation that is the holder of a licence under the Home Building Act 1989, and
must be authorised by the network operator to carry out the work.
Maximum penalty—
for a corporation—2,000 penalty units, or
for an individual—100 penalty units.
To ensure that a gas installation is safe to be supplied with gas from a gas network, a person carrying out work to which this section applies must, immediately before completing the work, conduct a leak test of the gas installation downstream of the gas meter.
Maximum penalty (subsection (4))—
for a corporation—2,000 penalty units, or
for an individual—100 penalty units.
A person conducting a leak test of a gas installation required by section 10(4) must, after completing the test, give written notice to the network operator and relevant consumer.
Maximum penalty—
for a corporation—2,000 penalty units, or
for an individual—100 penalty units.
If the test demonstrates the gas installation is safe to connect to the gas network, the notice must state—
the gas installation has been tested, and
the gas supply to the premises—
has been established or re-established, or
is ready to be established or re-established.
If the test demonstrates the gas installation is unsafe to connect to the gas network, the notice must state that the gas installation—
is defective, and
is unsafe to connect to the gas network.
The notice must include the following—
the name of the consumer,
the full address of the location,
the date and results of the test,
the name of the person who conducted the test and the name of the person’s employer, if any,
the number and details of the licence under the Home Building Act 1989 held by the person or the person’s employer,
if the notice is under subsection (3)—details of the faults identified.
The notice must be given to the network operator and consumer—
for a notice under subsection (2)—within 7 days after the test is conducted, and
for a notice under subsection (3)—as soon as practicable after the test is conducted.
The person who conducted the test must keep a copy of the notice given to the network operator and consumer for 5 years from the date on which it was issued.
Maximum penalty—
for a corporation—2,000 penalty units, or
for an individual—100 penalty units.
On receipt of a notice under subsection (2), a network operator must—
record the details of the notice, and
keep the record until the sooner of—
10 years after the date of the test, or
receipt of a further notice under this section in relation to the same gas installation.
Maximum penalty—
for a corporation—2,000 penalty units, or
for an individual—100 penalty units.
On receipt of a notice under subsection (3), a network operator must—
record the details of the notice, and
keep the notice until receipt of a further notice indicating—
the installation has been retested and that the gas installation is safe to connect to the gas network, and
the gas supply has been established or re-established, or is ready to be established or re-established.
Maximum penalty (subsection (8))—
for a corporation—2,000 penalty units, or
for an individual—100 penalty units.
A network operator must give the Secretary written notice if the network operator carries out unscheduled venting or flaring of gas in a gas network.
Maximum penalty—
for a corporation—2,000 penalty units, or
for an individual—100 penalty units.
The written notice must be given within 28 days after the venting or flaring is carried out.
In this section—
flaring, in relation to gas, means a controlled release of gas from a gas pipe involving the combustion of the released gas.
venting, in relation to gas, means a controlled release of gas from a gas pipe not involving the combustion of the released gas.