Loss monitoring for small storage systems
14 Loss monitoring for small storage systems
A system operator of a small storage system must not allow the small storage system to be in use unless a small storage system loss-monitoring procedure is carried out in respect of the system. Fine not exceeding 100 penalty units.
If a small storage system loss-monitoring procedure carried out under subregulation (1) in respect of a storage system detects, in a tank in the storage system, a variation in petroleum volume of more than 2% of the tank capacity, a system operator of the storage system must – notify an infrastructure owner of the storage system, within 7 days after the results of the procedure are received by the system operator, that the storage system is not providing full and continuous containment; and if petroleum may have been lost from the storage system, ensure that further petroleum is not lost from the storage system; and ensure that the storage system is not allowed to be in use until the tank is repaired or replaced in accordance with regulation 11. Fine not exceeding 100 penalty units.