reg 208

Earthing systems

In force
Part 2Electrical installations
Division 3Additional general wiring requirements

208 Earthing systems

(1)

A low voltage electrical installation required to be earthed must have an earthed neutral connection or a multiple earthed neutral (MEN) connection—

(a)

at the main switchboard; or

(b)

at an earth bar or link within a substation; or

(c)

made through an earthing conductor or terminal provided by the electricity supplier.

(2)

Subregulation (1) does not apply to an electrical installation installed for use at a mine (other than an underground mine) if that electrical installation is earthed using an earthing system that complies with AS/NZS 3007.

(3)

An electrical installation that is required to be earthed but is not connected to an electricity supplier's distribution system may use a system of earthing approved by Energy Safe Victoria.