reg 238
In forceHigh voltage conductors must not be supported along the façade of a building or structure
Part 2Electrical installations
Division 9Façade mounted wiring
238 High voltage conductors must not be supported along the façade of a building or structure
(1)
A high voltage conductor must not, at any time, be supported along—
(a)
the façade of a building or structure; or
(b)
any part of a building or structure that adjoins a public way or space.
(2)
Subregulation (1) does not apply to a high voltage conductor that is part of an electric security fence that complies with AS/NZS 3016.