10 Area in which chemical used or kept
An operator must ensure that any area on premises in which a chemical that can cause pollution is used or kept is within a compound which —
has walls that are impervious to acid;
has a floor that is impervious to acid; and
is capable of holding —
110% of the volume of the largest metal coating treatment tank or, if tanks are interconnected, 110% of the volume of the tanks in the interconnected system; and
not less than 25% of the total volume of the tanks within the compound.
An operator must ensure —
that storm water does not enter the area on the premises where metal coating treatment tanks are located; and
that the area on the premises where metal coating treatment tanks are located is designed to ensure that a liquid is not capable of overflowing or discharging from the area.