113 Ventilators
(1)
A water industry entity may cause a ventilating shaft, pipe or tube for any sewerage infrastructure or drain to be attached to the exterior wall of a building.
(2)
However, the mouth of a shaft, pipe or tube must be at least
1.8 metres higher than any window or door situated within a distance of
9 metres from its location.