reg 229

Minimum distances between aerial lines and the ground or water

In force
Part 2Electrical installations
Division 7Aerial lines and pole mounted substations

229 Minimum distances between aerial lines and the ground or water

(1)

A low voltage aerial line on public land or on private land not owned or leased by the owner of the line must not, at any time, be closer to—

(a)

the ground; or

(b)

the surface of any water that is not accessible to boats with masts—

than the relevant minimum distance specified in column 2 or 3 of Table 229.1 for the location of the aerial line set out in column 1 of that Table.

(2)

A high voltage aerial line set out in column 1 of Table 229.2 must not, at any time, be closer to—

(a)

the ground; or

(b)

the surface of any water that is not accessible to boats with masts—

than the relevant minimum distance specified in column 2, 3 or 4 of that Table that corresponds to that aerial line.

(3)

An aerial line must not, at any time, be closer than 13 500 millimetres to the surface of any water that is accessible to boats with masts.

(4)

The minimum distances specified in column 2, 3, or 4 of Tables 229.1 and 229.2 do not apply to a part of an aerial line that is within a substation.

(5)

In Tables 229.1 and 229.2—

arterial road has the same meaning as it has in the Road Management Act 2004;

freeway has the same meaning as it has in the Road Management Act 2004;

over-dimensional route means the roads and streets marked as an over-dimensional route on the Over Dimensional (OD) Route Network map, as published on the VicRoads website from time to time;

Port of Melbourne container route means the roads and streets marked as a container route on the Port of Melbourne Container Routes Network Map, as published on the VicRoads website from time to time.

Table 229.1—Minimum distances to the ground or water surface from low voltage aerial lines on public land or within an easement on private land

Type of aerial line

Column 1


Location of aerial line

Column 2


Bare live conductors

Column 3

Insulated live conductors

Minimum distance to ground or surface of water

Over a 2000 mm wide strip in the centre of each carriageway of a road

5500 mm

5500 mm

Over any other part of a freeway, arterial road, over‑dimensional route or Port of Melbourne container route

5500 mm

5500 mm

Over any other part of any other road

5500 mm

4900 mm

Over any part of a driveway

5500 mm

4600 mm

Over any other ground traversable by vehicles (other than a road)

5500 mm

4600 mm

At the connection to a building or structure (excluding a pole)

Not permitted

3000 mm

Over the surface of any water not accessible to boats with masts

4500 mm

4500 mm

Elsewhere

5000 mm

3000 mm

Table 229.2—Minimum distances to the ground or water surface from high voltage aerial lines

Minimum distance

Column 1





Type of aerial line
Nominal voltage ("U")

Column 2





Carriageway of roads

Column 3


Ground traversable by vehicles (other than a road)

Column 4

Other ground or the surface of any water not accessible to boats with masts

Alternating current insulated with earthed screen U > 1 kV

5500 mm

5500 mm

4500 mm

Alternating current insulated without an earthed screen
U > 1 kV

6000 mm

5500 mm

4500 mm

Bare or covered

1 kV a.c. or 1500V d.c.
< U ≤ 33 kV

6700 mm

5500 mm

5000 mm

Bare or covered

33 kV < U ≤ 132 kV

6700 mm

6700 mm

5500 mm

Bare or covered

132 kV < U ≤ 275 kV

8700 mm

7500 mm

6700 mm

Bare or covered

275 kV < U ≤ 330 kV

9700 mm

8000 mm

6700 mm

330 kV < U ≤ 500 kV

11 400 mm

10 700 mm

10 700 mm