reg 20

Clearances from aerial conductors—flammable materials

In force
Part 3Electricity network facilities

20 Clearances from aerial conductors—flammable materials

(1)

This section does not apply to a structure to which section 19 applies.

(2)

A person must not, without reasonable excuse, place or keep timber or other flammable material vertically below an aerial conductor.

Maximum penalty: 10 penalty units.

(3)

A person must not, without reasonable excuse, place or keep timber or other flammable material too close to an aerial conductor.

Maximum penalty: 10 penalty units.

(4)

Timber or other flammable material is too close to an aerial conductor if at any time it is within the minimum distance from any part of the conductor worked out in accordance with table 20.

Table 20

column 1column 2column 3column 4
direction in which minimum distance must be observedminimum distance from aerial conductor, where-
U  1 kV
minimum distance from aerial conductor, where-
1 kV < U  33 kV
minimum distance from aerial conductor, where-
33 kV < U  132 kV
horizontally, from any point of the vertical projection below the aerial conductor or aerial cable 3.0m3.0m3.0m

Note  Symbols used in table 20 are defined in the dictionary.