Requirements for toilets—Act, s 17 (1) (b)
16 Requirements for toilets—Act, s 17 (1) (b)
The following requirements are prescribed:
if a closet pan and cistern are to be installed—the pan must be a reduced-flush closet pan and the cistern a dual-flush reduced volume cistern;
if a closet pan only is to be installed—the pan must be a reduced‑flush closet pan;
if a cistern is to be installed that is connected to an existing full‑flush closet pan—the cistern must be a separate dual-flush cistern that—
is of at least 11L capacity; and
gives an effective full-flush not larger than 10L, and for test purposes, 9L; and
gives an effective half-flush not larger than 5.5L, and for test purposes, 4.5L;
if a cistern is to be installed that is connected to an existing reduced-flush closet pan—the cistern must be a dual-flush reduced volume cistern;
if a closet pan is to be flushed with water drawn from a central storage cistern installed before 1 January 1994 and—
the pan is a full-flush closet pan—the pan must be flushed with an effective full-flush not exceeding 10L and for test purposes, 9L; or
the pan is a reduced-flush closet pan—the pan must be flushed with an effective full-flush not exceeding 10L and for test purposes, either 6L or 9L;
the pan may be flushed with a half-flush of at least 4.5L and not exceeding 5.5L if a full-flush closet pan is to be flushed—
with water drawn from a central storage cistern; and
by control fittings that allow the user to decide whether to give a full-flush or half-flush;
the pan may be flushed with a half-flush of at least 3L and not exceeding 4L if a reduced-flush closet pan is to be flushed—
with water drawn from a central storage cistern; and
by control fittings that allow the user to decide whether to give a full-flush or half-flush;
if a central storage cistern installation is to be installed—
reduced-flush closet pans must be installed; and
control fittings must be installed that automatically control the amount of water used in a way that each flush uses—
on a full-flush—at least 6L and not exceeding 7L; or
on a half-flush—at least 3L and not exceeding 4L.
In this section:
dual-flush reduced volume cistern means a cistern that has the capacity to—
give an effective full-flush not exceeding 7L and for test purposes 6L; and
give an effective half-flush not exceeding 4L and for test purposes 3L.
full-flush closet pan means a closet pan that is a full-flush pan under AS 1172, as in force from time to time.
reduced-flush closet pan means a closet pan that is a reduced-flush pan under AS 1172, as in force from time to time.