Barrister AI
All legislation
QLDRegulation
In force
This is the latest official compilation.Check the official source →
reg 8

Using automatic fluoride dosing equipment for fluoride compounds

In force
Part 3Adding fluoride compounds
Division 3Automatic fluoride dosing equipment and operators

8 Using automatic fluoride dosing equipment for fluoride compounds

The public potable water supplier must use automatic fluoride dosing equipment that—

(a)

has the rate of feed of the fluoride compound paced to the flow of water into the public potable water supply; and

(b)

has at least 2 devices that independently monitor the flow of the water, at least 1 of which measures the rate of flow of the water; and

(c)

is designed in a way that ensures if part of the equipment fails, the fluoride compound is not added to the water supply.