Minimum distances between materials, protected aerial lines and protected infrastructure
611 Minimum distances between materials, protected aerial lines and protected infrastructure
A person must not place any flammable material or allow flammable material to remain closer than 3000 millimetres in any direction from a wall or fence of any substation or switch yard that forms part of protected infrastructure.
Penalty: 20 penalty units.
A person must not place any flammable material or allow flammable material to remain vertically below a protected aerial line.
Penalty: 20 penalty units.
A person must not place any flammable material or allow flammable material to remain so that, at any time, the flammable material is closer than the relevant horizontal distance specified in Row A of Table 611 from any point of the vertical projection below a protected aerial line.
Penalty: 20 penalty units.
A person must not place any material or allow any material to remain so that, at any time, the material is closer than the relevant horizontal distance marked "h" specified in Row B of Table 611 from any point of the vertical projection below a protected aerial line unless the material is no closer vertically below the line than the vertical distance marked "v" specified in Row B of Table 611.
Penalty: 20 penalty units.
Table 611—Minimum distances from materials to protected aerial lines
Column 1 | Column 2 | Column 3 | Column 4 | Column 5 | Column 6 | Column 7 |
Aerial lines | ||||||
| U ≤ 1500V |
|
|
|
|
|
Row A Flammable material Horizontal distance |
|
|
|
|
|
|
Row B Any other material |
|
|
|
|
|
|
"v" | 3700 mm | 4600 mm | 4600 mm | 6800 mm | 8000 mm | 9800 mm |
The statute text is free to read above. View Pro plans to unlock the case-law research tools for each provision.