Barrister AI
All legislation
VICRegulation
In force
This is the latest official compilation.Check the official source →
reg 613

Minimum distances between transported loads and protected aerial lines

In force
Part 6Duties of the public

613 Minimum distances between transported loads and protected aerial lines

A person must not drive or manoeuvre a vehicle with a load or transport a load so that the load is closer to a protected aerial line set out in Row A of Table 613 than the relevant minimum distance specified in Row B of that Table that corresponds to that protected aerial line.

Penalty: 20 penalty units.

Table 613—Minimum distances from transported loads to protected aerial lines

Column 1

Column 2

Column 3

Column 4

Column 5

Column 6

Column 7

Alternating current aerial lines
Nominal voltage ("U")

Row A

Aerial line

U ≤ 1 kV a.c. bare conductor and
U ≤ 1500V d.c. traction conductor




U ≤ 1 kV a.c. insulated conductor

1 kV<
U ≤ 66 kV a.c. and
1500V < U ≤ 66 kV d.c.




66 kV<
U ≤ 132 kV





132 kV<
U ≤ 275 kV





275 kV<
U ≤ 330 kV




330 kV<
U ≤ 500 kV

Row B

Minimum distance from the aerial line in all directions




600 mm




300 mm




1000 mm




1500 mm




3200 mm




3700 mm




4700 mm