reg 13.2
In forceIf the system is connected to a vacuum toilet, the system must be vacuum tested in accordance with clauses 16.15.2 and 16.15.3 of AS/NZS 3500.2.
13.2 If the system is connected to a vacuum toilet, the system must be vacuum tested in accordance with clauses 16.15.2 and 16.15.3 of AS/NZS 3500.2.
13.3 If the system is connected to a macerator toilet, the system must be air pressure tested to withstand air pressure of 10 kilopascals while the pressure gauge is stationary for 10 minutes.