reg 13

Standards prescribed for particular areas

In force

13 Standards prescribed for particular areas

(1)

In this section —

customer premises means premises on which electrical installations are connected to a transmission or distribution system for the purpose of receiving supply.

(2)

A transmitter or distributor must, so far as is reasonably practicable, ensure that for customer premises in an area referred to in the first column of the Table to this subsection the average total length of interruptions of supply, as calculated under subsection (3), does not exceed the number of minutes specified in the second column opposite the reference to that area.

Table

Area

Standard for average total length of interruptions

the Perth CBD

30

the urban areas other than the Perth CBD


160

any other area of the State

290

(3)

For the purposes of subsection (2), the average total length of interruptions of supply is to be calculated as at 30 June in each year —

(a)

by taking the average total length, in minutes, of interruptions of supply to customer premises in an area during each year of the period of 4 years ending on that day; and

(b)

by then taking the average of the 4 annual figures determined under paragraph (a).

(4)

Each customer premises, or part of such premises, for which the supply of electricity is metered separately under the Energy Operators (Powers) Act 1979 section 62(5) are separate premises for the purposes of this section.